Technical and Economic Analysis of Solar PV/Diesel Generator Smart Hybrid Power Plant Using Different Battery Storage Technologies for SRM IST, Delhi-NCR Campus.

Item request has been placed! ×
Item request cannot be made. ×
loading   Processing Request
  • معلومة اضافية
    • نبذة مختصرة :
      This paper presents atechnical and economic analysis of the proposed solar PV/diesel generator smart hybrid power plant for a part of SRM IST, Delhi-NCR campus. The analysis was performed using five battery storage technologies: lead-acid, lithium-ion, vanadium flow, zinc bromide and nickel-iron. The analysis also used the HOMER Pro software. The analysis was conducted to assess performance parameters such as initial cost, simple payback period, return on investment, energy produced, renewable penetration and emission of air pollutants. The optimal solution was obtained as SPP(200 kW)/DG(82 kW)/ZB(2000 kWh), with cycle charging dispatch strategy. The initial cost of this configuration is estimated to be USD163,445, and the operating cost is USD534 per year. The net present cost is estimated to be USD170,348, and the estimated cost of energy with this configuration has been obtained as USD0.090 per kWh. It is estimated that with this optimal solution, the diesel generator may consume only 110 L/year of diesel, which is the minimum of all configurations. Sensitivity analysis was performed between the size of the solar PV array and the size of the battery, along with variations in the battery's nominal capacity and renewable fraction. [ABSTRACT FROM AUTHOR]